Notifications
You must be signed in to change notification settings - Fork 51
Open
Description
I'm trying to obtain data from an Aira heat pump which has an existing and operational data connection between itself and a Carlo Gavazzi ET340 energy meter.
I've tapped into the Modbus bus and have found the communication settings used - 19200 baud, 8 bits, even parity...
However, I get continuous CRC errors, for example:
14.05.2025 09:57:07.113 'Port' Info: Start polling
14.05.2025 09:57:07.113 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:07.298 'Device' Rx: 02 03 28 FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF 44 DA 02 03 2B D3 00 14 BD EB 02 03 28 32 34 30 38 30 37 31 30 38 31 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 4C BC
14.05.2025 09:57:07.299 'Device' Error: RTU. Wrong CRC
14.05.2025 09:57:08.075 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:08.267 'Device' Rx: 02 03 08 47 00 B6 41 02 03 26 00 00 00 00 00 00 01 18 00 72 00 06 F5 F8 00 00 0E 30 0B B8 0B B8 00 00 10 92 10 B3 12 51 79 12 25 0B B8 00 00 0A DF
14.05.2025 09:57:08.269 'Device' Error: RTU. Wrong CRC
14.05.2025 09:57:09.076 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:09.252 'Device' Rx: 14 04 00 34 00 02 32 C0 14 04 04 14 00 00 FA 7D
14.05.2025 09:57:09.252 'Device' Error: RTU. Wrong CRC
14.05.2025 09:57:10.077 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:10.144 'Device' Rx: 02 03 28 32 34 30 38 30 37 31 30 38 31 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 4C FE 00 14 BD EB
14.05.2025 09:57:10.145 'Device' Error: RTU. Wrong CRC
14.05.2025 09:57:11.078 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:11.251 'Device' Rx: 14 04 00 00 00 06 72 CD 14 04 0C 09 A1 00 00 00 00 00 00 00 00 00 00 5A 5A
14.05.2025 09:57:11.253 'Device' Error: RTU. Wrong CRC
14.05.2025 09:57:12.080 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:12.189 'Device' Rx: 02 03 2B 70 00 14 4D C9
14.05.2025 09:57:12.190 'Device' Error: Not correct response. Requested unit (unit) is not equal to responsed
14.05.2025 09:57:13.082 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:13.220 'Device' Rx: 02 06 07 CF 00 00 B8 B2 02 06 07 CF 00 00 B8 B2
14.05.2025 09:57:13.222 'Device' Error: RTU. Wrong CRC
14.05.2025 09:57:14.082 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:14.267 'Device' Rx: 14 04 00 0C 00 06 B2 CE 14 04 0C 01 80 00 00 00 00 00 00 00 00 00 00 14 B9
14.05.2025 09:57:14.268 'Device' Error: RTU. Wrong CRC
14.05.2025 09:57:15.082 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:15.236 'Device' Rx: 02 03 2B 98 00 14 CD FD
14.05.2025 09:57:15.237 'Device' Error: Not correct response. Requested unit (unit) is not equal to responsed
14.05.2025 09:57:16.085 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:16.205 'Device' Rx: 02 03 08 33 00 14 B7 99
14.05.2025 09:57:16.206 'Device' Error: Not correct response. Requested unit (unit) is not equal to responsed
14.05.2025 09:57:17.085 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:17.283 'Device' Rx: 14 04 00 34 00 02 32 C0 14 04 04 14 00 00 FA 7D
14.05.2025 09:57:17.284 'Device' Error: RTU. Wrong CRC
14.05.2025 09:57:18.084 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:18.190 'Device' Rx: 02 03 28 32 34 30 38 30 37 31 30 38 31 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 4C BC
14.05.2025 09:57:18.191 'Device' Error: Not correct response. Requested unit (unit) is not equal to responsed
14.05.2025 09:57:19.085 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:19.283 'Device' Rx: 02 03 2B 98 00 14 CD FD 02 03 28 31 30 30 30 37 35 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 AE BB
14.05.2025 09:57:19.284 'Device' Error: RTU. Wrong CRC
14.05.2025 09:57:20.085 'Device' Tx: 01 03 00 00 00 0A C5 CD
14.05.2025 09:57:20.283 'Device' Rx: 02 03 08 47 00 B6 41 02 03 26 00 00 00 00 00 00 01 18 00 72 00 06 F5 F8 00 00 0E 30 0B B8 0B B8 00 00 10 92 10 A4 12 51 79 12 25 0B B8 00 00 44 6B
14.05.2025 09:57:20.284 'Device' Error: RTU. Wrong CRC
14.05.2025 09:57:20.742 'Port' Info: Finish polling
Now I don't think it's necessarily a problem with the ModbusTools application, probably just some strange communication setting. But I have no idea how to troubleshoot.
Can you offer any advice?
Many thanks for this amazing looking open source software BTW!